CE 110 Specs
Typical Installation
Submittal Drawing
Submittal Specs
Operating Manual
Back to CE 110 Intro
CE 110 Submittal Drawing

PC Number

  Description

1

Jacket Blue-Green Enamel

2

Heating Element 1000 Watts, 120V

3

Thermostat 110-170oF

4

Stainless Steel Tank - 1 Gallon

5

Hi Limit Manual Reset - 190oF

6

Access Plate To Hi-Limit

7

Cold Water Inlet - 1/4" Male NPT

8

Hot Water Inlet - 1/4" Male NPT

9

Front Cover

10

Electrical Service Entrance

11

Insulation Fiberglass 1" Thick

12

T&P Relief Valve Opening

Optional Equipment:

  • Tempering valve to increase the supply of hot water to 11.5 GPH 45-110oF
  • 450 watt model, please specify model CE110-450 W rated 4 amp at 120 V

Notes:

  1. Unit rated for 150 psi WP
  2. Recovery rated 6.3 GPH 45-110oF and will draw 8.3 amps at 120 V, 1 PH
  3. Unit supplied with two (2) wall mounting brackets
  4. Unit supplied with T&P relief valve set at 150 psi and 210oF

Typical Lavatory Installation

Wiring Diagram

 

Hot Water Heaters Home | Hot Water Heaters Selection Guide | Rep Listing | Contact Hubbell Heaters

Low Capacity Electric Water Heaters | High Capacity Electric Water Heaters | Special Purpose Water Heaters | Steam Fired Water Heaters | Indirect / Direct Fired Water Heaters | Heating Elements & Coils

Hubbell HeaterswThe Electric Heater CompanywP.O.Box 288 wStratford, CT 06615-0288
Phone: (203) 378-2659
wFax:(203) 378-3593wEmail: info@hubbellheaters.com