Specifications
Std/Opt. Equipment
Outline Dimensions
Sizing Formulas
KW, GPM, Amperage
Ordering Information
Operating Manual
Back to D Intro
Model D KW, GPM, Amperage Chart

GPM Heating Capacity With Amperage Chart

KW
Rating

GPM Recovery Rating
At oF Temp. Rise

Amp Draw By Voltage & Phase

208V

240V

480V

40oF

60oF

80oF

100oF

120oF

140oF

1F

3F

1F

3F

3F

6

1.0

0.7

0.5

0.4

0.3

0.2

29

17

25

15

7

8

1.4

0.9

0.7

0.6

0.5

0.4

38

22

33

19

10

10

1.7

1.1

0.8

0.7

0.6

0.5

48

28

42

24

12

12

2.0

1.4

1.0

0.8

0.7

0.6

58

33

50

29

15

15

2.6

1.7

1.3

10.

0.8

0.7

72

42

62

36

18

20

3.4

2.3

1.7

1.4

1.1

1.0

96

56

83

48

24

24

4.1

2.7

2.0

1.6

1.4

1.2

115

66

100

58

29

30

5.1

3.4

2.6

2.1

1.7

2.5

144

83

125

72

36

35

6.0

4.0

3.0

2.4

2.0

2.7

169

97

146

84

42

40

6.8

4.5

3.4

2.7

2.3

2.0

192

111

167

96

48

45

7.7

5.1

3.8

3.1

2.6

2.2

216

125

188

108

54

54

9.2

6.1

4.6

3.7

3.1

2.6

259

150

226

130

65

58

9.9

6.6

4.9

4.0

3.3

2.8

279

162

243

139

70

 

Hot Water Heaters Home | Hot Water Heaters Selection Guide | Rep Listing | Contact Hubbell Heaters

Low Capacity Electric Water Heaters | High Capacity Electric Water Heaters | Special Purpose Water Heaters | Steam Fired Water Heaters | Indirect / Direct Fired Water Heaters | Heating Elements & Coils

Hubbell HeaterswThe Electric Heater CompanywP.O.Box 288 wStratford, CT 06615-0288
Phone: (203) 378-2659
wFax:(203) 378-3593wEmail: info@hubbellheaters.com