Model F Dimensional And Connection Sizing
F30
F60
F90
F120
Height "A"
45"
49"
57"
58"
Width "B"
26"
Length "C"
39"
Cold Water Inlet(Male NPT)
1 1/2"
2"
2 1/2"
Hot Water Outlet(Female NPT)
Steam Inlet(Female NPT)
3"
3 1/2"
4" FLG
Main Condensate(Trap Size)
1"
1 1/4"
Drip Trap Size
1/2"
SteamConsumptionFormula
GPM x 500 x DT = Lbs./Hr.SteamLatent heat of_________ Steam
Steam Pressure (psi)
0
2
5
10
15
20
25
30
40
50
Latent Heat
970
966
960
953
946
939
933
929
920
912