WATER
HEATER OPERATIONAL FEATURES
Packaged with the Hubbell model EMV hot water heater is a
triple redundant, thermostatic pressure balanced
valve designed pecifically for emergency
safety shower/face/eyewash applications. The
valve is factory mounted and piped to the water
heater. After water flow is activated at the
emergency station, the outlet water temperature
from the model EMV package will be maintained
at 85°F tepid temperature. The Hubbell EMV is
able to achieve the high volume demand
required for a safety drench system by mixing
the 170°F water in the tank with incoming cold
water. The mixing valve meets OSHA and ANSI
requirements and is capable of providing
constant 85°F output regardless of inlet
pressure and temperature variations, and the
temperature setting is tamper proof and cannot
be inadvertently adjusted in the field. The water
temperature is not warm enough to open skin
pores and not cold enough to deter usage. The
valve is capable of providing a full range of
flows from the smallest flow of 0.4 GPM for an
eyewash to the combined 23 GPM flow for a
simultaneous demand of shower, eyewash, and
face wash system.
WATER
HEATER SAFETY FEATURES
The mixing
valve incorporates a pressure sensing controller with a valve actuator
hat
senses the water pressure on both the hot and
cold water inlet connections. If hot water
pressure is not present then the actuator overrides
the mixing valve and a flow of cold water is allowed.
|

If no
cold-water pressure is available at
the mixing valve inlet then the hot water port will
close to prevent overheated water from exiting the
mixing valve. The valve also includes a safety
override feature that continuously senses the final
mixed water temperature. If the final water
temperature is overheated, the valve automatically
closes the hot water port and fully opens the cold
water port. In any of these fault conditions, the
Hubbell EMV valve will continue to provide a full
flow of water as per the ANSI standard with no
additional pressure drop.
|