- All
welded carbon steel vessel designed and built in strict
accordance with the ASME Code Section IV and stamped, certified,
and registered with the National Board of Boiler and Pressure
Vessel Inspectors.
- All
internal tank surfaces are lined with a minimum of 5/8"
thick Hydrastone cement for superior protection and tank
longevity.
- Designed
for 100psi working pressure and hydrostatically tested
at 150psi (1½ times the WP).
|
Vessel
(options)
- Alternate
protective lining:
phenolic epoxy resin.
- Alternate
vessel construction:
Stainless Steel Type 304 or 316L, 90/10 Copper-Nickel, other.
- Alternate working pressure:
please specify
|
General
- Heavy
duty 2" thick fiberglass blanket insulation covers the
pressure vessel for maximum operating efficiency and minimal
standby heat loss.
- Heavy
gauge galvanized steel protective jacket holds insulation
in place and protected to ensure highly efficient operation.
- Integrally
welded bulkhead attachment points.
- Entire
vessel is supported on heavy duty integrally welded steel
supports for sturdy deck mounting.
- Full
five (5) year Non Pro-Rated tank warranty and one (1) year
electrical component warranty.
- Bronze
ASME rated combination temperature and pressure safety
relief valve set at the vessel working pressure and 210°F.
- ABS
approved and in conformance with USCG regulations.
|
General
(options)
- Skid
mounting on heavy duty all wedled I beam.
- Type
304 stainless steel protective jacket, please specify if
painted.
- Dual
energy package provides operational flexibility for electric
and (steam or boiler water) power.
|
Electrical
Operationg Controls
- All
electrical operating controls are factory sized, selected,
wired, tested, and mounted in a NEMA 1 enclosure to ensure
safe and reliable operation.
- A
power distribution block is supplied for single point electrical
installation.
- Power
fuses rated at maxmimum of 60 Amps protect each heating
element branch circuit per NEC and UL requirements. Each
branch circuit has a maximum rating of 48 Amps.
- Heavy
duty definite purpose magnetic contactor with integrally
mounted power fuse block assembly switches power on/off
to each branch circuit.
- Heavy
duty removable flange type copper sheathed immersion heating
element provides long service life.
- Fully
adjustable thermostat maintains accurate water temperature
and is sized by the factory to control the appropriate
number of heating element circuits.
- A
generously sized transformer provides fused 120V to the
control circuit.
- A
fully adjustable (100-240°F) safety hi-limit device
with manual reset interrupts power to the control circuit
in the event of over-temperature water in the storage tank.
- Safety
door interlock mechanism interrupts power to the control
circuit upon opening the electrical control panel.
- Louvers
in the control panel allow for cooling of the electrical
components to ensure maximum electrical component longevity
(when required).
|
Electrical (options)
- NEMA
4 watertight enclosure for outdoor/wet locations.
- Explosion resistant enclusure for hazardous locations.
Please specify class, division, and group.
- Built-incircuit breaker (with or without shunt trip) or
a built-in non-fused On/Off disconnect switch.
- Alternate element sheath material (please specify: Incoloy,
Stainless Steel, other).
- Specialiazed
heating element construction including: Special watt density
rating, passivation, electropolishing, hermetic seals,
or any other feature required to meet the needs of your
application.
- Factory
installed low water cut out device to disengage electrically
the heating element(s) in the event of insufficient water
in the tank.
- Dial
thermometer and pressure gauge factory installed in the
tank.
- Intra-tank
circulation pump package with On/Off switch to continuously
circulate water within the tank and thereby reduce stratification.
All bronze circulator pump is rator 1/12 HP, 120V, 1 Ph.