Model PS Recovery Rates

Recovery Ratings & Heating Coil Selection

Temperature Rise oF
(From-To)

GPH
Heated

Heating  Coil
Model

40-110

343

D1

40-120

300

D2

40-140

240

D3

40-160

200

D4

40-180

171

D5

50-110

400

F1

50-120

343

F2

50-140

267

F3

50-160

218

F4

50-180

185

F5

60-110

480

H1

60-120

400

H2

60-140

300

H3

60-160

240

H4

60-180

200

H5

Note: Maximum steam consumption is 211 Lbs/Hr for all of the above recoveries.

Steam Operating Controls Sizing

Steam
Pressure

Control
Valve

Steam
Strainer

Drip
Trap

Main
Trap

0 – 10 psi

1"

1"

1/2"

1/2"

11 - 25 psi

3/4"

3/4"

1/2"

1/2"

25 - 125 psi

1/2"

1/2"

1/2"

1/2"

 