GENERAL Provide a quantity of _______ commercial electric water heater(s) Model No. _____________as manufactured by
HUBBELL Electric Heater Co., Stratford, CT. The entire unit is to be complete with all operating controls and require only plumbing and electrical service connections. The tank shall be all welded steel commercial
construction designed for 150psi working pressure and contain _________gallons of storage. The tank is to be lined with seamless Hydrastone cement to a minimum thickness of 1/2" on 100% of all interior tank
surfaces (rOptional Specification: tank to be fabricated from solid copper-silicon )
and shall not require any type of anodic protection. The tank shall be designed and fabricated with non-ferrous copper-silicon threaded tappings and non-ferrous inlet and outlet piping for maximum corrosion resistance. Steel tank tappings will not be acceptable. The entire tank is to be insulated with a minimum of 2" thick polyurethane foam insulation and exceed the latest ASHRAE standard for stand-by heat loss. The complete heater shall be supplied with a high impact colorized composite protective jacket which cannot rust or corrode and does not require painting.
The cold water inlet shall be 3/4" Female NPT ( rOptional Specification: 11/2" Male NPT )
and include a non-corrosive strata-flow diffuser which prevents incoming cold water from mixing too rapidly with hot water in the tank. A 3/4" hose connection drain is supplied. The hot water outlet shall be 3/4" Male NPT
(rOptional Specification: 11/2" Male NPT )
and shall include a factory installed built-in heat trap to prevent water from radiating through the piping during stand-by periods. A separate 3/4" Female NPT tapping is to be provided for relief valve installation. An ASME rated automatic reseating combination temperature and pressure safety relief valve set at 150psi and 210
oF shall be factory supplied. RECOVERY The heating element(s) shall be a high quality incoloy sheath electric immersion type
and shall be rated at ________KW which will heat _______GPH of water at ______oF Rise ( _______ o to _______ oF). ELECTRICAL The heater shall be designed to operate at _______volts ______ phase ______ Hz (balanced) with all necessary operating
controls factory mounted, wired and tested. Each circuit is to be independently operated through a definite purpose magnetic contactor having a resistive load rating exceeding the ampere rating of that particular
circuit. Water temperature shall be controlled through an adjustable snap action surface thermostat (rOptional Specification:
an immersion thermostat 100-180oF or 30-110oF ). An over-temperature manual reset Hi-Limit shall be factory installed to disconnect all conductors to the heating element(s) in the
event of an over-temperature condition in the pressure vessel. In addition, the water heater shall be supplied with the following optional features:
r Option _________________ rOption _________________ rOption _________________
The water heater manufacturer shall warranty all electrical components against defects in workmanship and material for a period of one (1) year from date of start-up, and the pressure vessel for a full five (5) years
Non Pro-Rated (rOptional Specification: full ten (10) years Non Pro-Rated ) from date of start-up, provided that the unit is
started within three (3) months of date of shipment and installed and operated within the scope of the tank design and operating capability. Each water heater shall be shipped with a complete set of installation and
operating instructions including spare parts list and approved drawings. |