SH & H Tank Types
Standard Features
Optional Equipment
SH & H Dimensions
Outline Drawings
Amperage Chart
SH & H Formulas
Ordering Information
Submittal Specs
Operating Manual
To Model SH&H Intro
SH/H Model Standard Equipment

nVessel Construction

  1. All welded carbon steel vessel designed and built in strict accordance with the ASME Code Section IV and stamped, certified, and registered with the National Board of Boiler and Pressure Vessel Inspectors.
  2. All internal tank surfaces are lined with a minimum of 5/8" thick Hydrastone cement for superior protection and tank longevity.
  3. Designed for 125psi working pressure and hydrostatically tested at 188psi (11/2 times the WP).

nGeneral

  1. Heavy duty 2" thick fiberglass blanket insulation covers 100% of the pressure vessel for maximum operating efficiency and minimal standby heat loss.
  2. Heavy gauge galvanized steel protective jacket with both top and bottom heads keeps insulation in place and protected to ensure high efficiency during operation.
  3. Entire vessel is supported on heavy duty integrally welded steel supports for sturdy floor mounting.
  4. Full five (5) year Non Pro-Rated tank warranty and one (1) year electrical component warranty.
  5. Bronze ASME rated combination temperature and pressure safety relief valve set at the vessel working pressure and 210oF.

nElectrical Operating Controls

  1. All electrical operating controls are factory sized, selected, wired, tested, and mounted in a NEMA I enclosure to ensure safe and reliable operation.
  2. A power distribution block is supplied for single point electrical installation.
  3. Fast acting power fuses rated at a maximum of 60 Amps protect each heating element branch circuit per NEC and UL requirements.  Each branch circuit has a maximum rating of 48 Amps.
  4. Heavy duty definite purpose magnetic contactor with integrally mounted power fuse block assembly switches power on/off to each branch circuit.
  5. Heavy duty removable flange type copper sheathed immersion heating element provides long service life.
  6. Fully adjustable thermostat maintains accurate water temperature and is sized by the factory to control the appropriate number of heating element circuits.
  7. A generously sized transformer provides fused 120V to the control circuit
  8. A fully adjustable (100-240oF) safety hi-limit device with manual reset interrupts power to the control circuit in the event of over-temperature water in the storage tank.
  9. Safety door interlock mechanism interrupts power to the control circuit upon opening the electrical control panel.
  10. Louvers in the control panel allow for cooling of the electrical components to ensure maximum electrical component longevity.
 

Hot Water Heaters Home | Hot Water Heaters Selection Guide | Rep Listing | Contact Hubbell Heaters

Low Capacity Electric Water Heaters | High Capacity Electric Water Heaters | Special Purpose Water Heaters | Steam Fired Water Heaters | Indirect / Direct Fired Water Heaters | Heating Elements & Coils

Hubbell HeaterswThe Electric Heater CompanywP.O.Box 288 wStratford, CT 06615-0288
Phone: (203) 378-2659