Tank Types
Standard Equipment
Optional Equipment
Dimensions
Outline Dimensions
Steam Controls
Control Valves
Formulas
Ordering Info
Submittal Specs
Operating Manual
Back to ST Intro
Steam Consumption Formula

  GPH X    oF D T x 8.33
__________________________________________  =      Lbs/Hr Steam
              Latent Heat of Steam

Steam Pressure (psi)

0

2

5

10

15

20

25

30

40

50

Latent Heat

970

966

960

953

946

939

933

929

920

912

Note:
For detailed information regarding the heating coil, please review the brochure titled "Hubbell Heating Coils."

Metric Conversions

Liters x 0.2641 = Gallons
Gallons x 3.79 = Liters
Gallons x 0.003785 = m3
m3 x 264.2 = Gallons
1
oC DT = 1.8oF DT
oF = (oC x 1.8) + 32
oC = (oF - 32) x 0.556
psi x 0.06896 = Bar
Bar x 14.5 = psi
psi x 6.86 = kPa
kPa x 0.1456 = psi
Lbs x 0.4536 = Kg
Kg x 2.2 = Lbs
Watts/Sq.Cm. x 6.4 = Watts/Sq.In.
Watts/Sq.In. x 0.155 = Watts/Sq.Cm.

 